Gas Pressure Regulator RMG 502

Pilot-operated Gas Pressure Regulator According to DIN EN 334 (operating with auxiliary energy from the inlet pressure range)

Gas Pressure Regulator RMG 502

Application

  • Device for transfer stations in gas transport networks for power plants and industrial facilities
  • Wide inlet pressure range
  • Pilot Series RMG 630
  • RMG 630-1 (formerly RMG 640), singlestage type for inlet pressure varation < 15 bar
  • Outlet DN double as inlet DN
  • Less parts, easy to maintain, quiet operation
  • Grid plate for noise reduction
  • Also available with metal foam for additional noise reduction
  • Suitable for non-aggressive gases, other gases on enquiry
  • CE-registration according to PED
 
Max. admissible pressure PS =100 bar
Max. inlet pressure pu max up to 100 bar
Outlet pressure range Wd 0.3 bar to 90 bar
Min pressure drop approx. 1.5 bar, others on enquiry
Max. pressure drop 90 bar
Class of lock-up pressure zone SZ 2.5
Connection - Flange PN 40 and
- Flange Class 300,
Class 600 according to ANSI 16.5
With pipe sizes inlet/outlet
- DN 25/50, DN 50/100, DN 80/150,
DN 100/200, DN 150/300, DN 200/300

All mechanical components of this device are without potential ignition sources and / or hot faces. They are not subject to ATEX 95 (94/9/EC).
All electronic accessories, on the other hand, meet ATEX requirements.

Copyright MAXXmarketing Webdesigner GmbH